For more info: sales@tangkasanugerah.com

Home / Products

PLR Series

Features

  • Output Voltage Rating:20V / 36V / 60V
  • Output Power:360W / 720W
  • Low Ripple and Noise (0.5mVrms/ 10mArms)
  • Fast transition recovery time(100us)
  • Maximum 2 units in series connections or 3 units in parallel connections
  • Select the setting digits for voltage and current(coarse/ fine volume control)
  • Panel Lock Function
  • 3 set of preset function
  • Output off timer function(Range:1 min to 1000 hours & 59mins)
  • CC priority function(prevent overshoot & inrush current)
  • Sequence function of PC editing(Max.: 1000 steps/ Min. step period: 50ms)
  • Protection: OVP, UVP, OCP, remote sensing(Terminal open)
  • External Analog Control Function
  • PC Remote Interface (Standard):RS-232; (Optional) : GPIB / USB / LAN
  • CE Compliance

DESCRIPTION

The single power output ranges are 360W and 720W. The series comprises 6 models and the voltage ranges are 20V, 36V and 60V.  The PLR series is a hybrid circuit design which incorporates front stage switching and rear stage linear architectures. The unique advantages of this design benefit from the combination of both switching and linear structures. The front stage switching structure can effectively reduce size and weight, and the rear stage linear structure can maintain lower ripple voltage, lower ripple current, and faster transient response.  

FEATURES

Model

PLR20-18

PLR20-36

PLR36-10

PLR36-20

PLR60-6

PLR60-12

OUTPUT  RATING

Voltage

0V to 20V

0V to 36V

0V to 60V

Current

0 ~18A

0 ~36A

0 ~10A

0 ~20A

0 ~6A

0 ~12A

Power

360W

720W

360W

720W

360W

720W

REGULATION (CV)

Load

0.005%FS+2mV

0.005%FS+2mV

0.005%FS+2mV

Line

0.005%FS+1mV

0.005%FS+1mV

0.005%FS+1mV

REGULATION (CC)

Load

5mA

5mA

5mA

Line

5mA

10mA

1mA

5mA

1mA

5mA

RIPPLE & NOISE (Noise Bandwidth= 20MHz ; Ripple Bandwidth = 1MHz)

CV p-p

30mVp-p

30mVp-p

30mVp-p

CV rms

0.5mVrms

0.5mVrms

0.5mVrms

CC rms

10mArms

5mArms

10mArms

5mArms

5mArms

SETTING ACCURACY  (23°C±5°C, after 30-minute aging)

Voltage

± (0.5%SET+0.5%F.S):

± (0.5%SET+0.5%F.S):

± (0.5%SET+0.5%F.S):

Current

± (1%SET+1%F.S):

± (1%SET+1%F.S):

± (1%SET+1%F.S):

Power

±(0.7%rdg+1.5%F.S):

±(0.7%rdg+1.5%F.S):

±(0.7%rdg+1.5%F.S):

READBACK ACCURACY (23°C±5°C, after 30-minute aging)

Voltage

±(0.1%rdg+2digit):

±(0.1%rdg+2digit):

±(0.1%rdg+2digit):

Current

±(0.5%rdg+2digit):

±(0.5%rdg+2digit):

±(0.5%rdg+2digit):

RESPONSE TIME

Raise Time

50ms/50ms: No load/Rated load
Output voltage: 10%→90%FS

50ms/50ms: No load/Rated load
Output voltage: 10%→90%FS

50ms/50ms: No load/Rated load
Output voltage: 10%→90%FS

Fall Time(Full load)

50ms ; Output voltage: 90%→10%FS

50ms ; Output voltage: 90%→10%FS

150ms ; Output voltage: 90%→10%FS

Fall Time(No load)

250ms ; Output voltage: 90%→10%FS

250ms ; Output voltage: 90%→10%FS

600ms ; Output voltage: 90%→10%FS

Load Transient Recover Time
(Load change from 50 to 100%)

100μs

100μs

100μs

SETTING RESOLUTION

Voltage

10mV

10mV

10mV

Current

10mA

10mA

10mA

MEASUREMENT RESOLUTION

Voltage

10mV

10mV

10mV

Current

10mA

10mA

10mA

SERIES AND PARALLEL CAPABILITY

Parallel Operation

Up to 3 units

Up to 3 units

Up to 3 units

Series Operation

Up to 2 units

Up to 2 units

Up to 2 units

PPROTECTION FUNCTION

OVP

Set range: 10% to 110% FS. Set resolution: 10 times the minimum display resolution.
Activated when the output voltage exceeds the set OVP value: Hardware detection.

OCP

Set range: 5% to 110% FS. Set resolution: 10 times of minimum display resolution.
Activated when the output current exceeds set OCP value: Software detection.

UVP

Set range: -1V to 110% FS. Set resolution: 10 times the minimum display resolution.
Activated when the output voltage falls below the set UVP value: Software detection.

ENVIRONMENT CONDITION

Operation Temp

0℃to40℃

Storage Temp

﹣20℃ to 60℃

Operating Humidity

30% to 85% RH (No dew condensation)

Storage Humidity

20% to 85% RH (no dew condensation)

READ BACK TEMP WEFFICIENT

Voltage

±100ppm/℃

±100ppm/℃

±100ppm/℃

Current

±100ppm/℃

±100ppm/℃

±100ppm/℃

OTHER

Power consumption

570VA

1100VA

520VA

1050VA

510VA

1000VA

Power factor

0.99

0.99

0.99

Coolingmethod

Forced cooling: Fan speed proportionate to the temperature of the internal heat sink.

Power Source

Single-phase 100VAC to 240VAC, 50Hz to 60Hz

Interface

   RS-232C/LAN (Standard: )    ;   GPIB/USB (option)

Analog Control

Yes

Dimension 

139.5 (H) * 140(W)
 *415.5(D)

139.5 (H) * 210(W)
 *415.5(D)

139.5 (H) * 140(W)
 *415.5(D)

139.5 (H) * 210(W)
 *415.5(D)

139.5 (H) * 140(W) *415.5(D)

139.5 (H) * 210(W) *415.5(D)

Weight

5.2kg

7.5kg

5.2kg

7.5kg

5.2kg

7.5kg

  (The specifications apply when the PLR is powered on for at least 30 minutes to warm-up to a temperature of20 ℃ to30 ℃,  unless specified 

Subscribe now